• Power supply: 10.8 - 26.8 Vdc • Operating distance: 100m • Protection: IP55
|
Model |
FLR100 |
|
Power Supply Voltage |
10.8 – 26.8 Vdc |
|
Consumption in Idle @ 24 Vdc (Tx, Rx, Tx/Rx) |
55 mA, 45 mA, 55 mA |
|
Consumption in Idle @ 12 Vdc (Tx, Rx, Tx/Rx) |
45 mA, 35 mA, 45 mA |
|
Consumption in Alarm @ 24 Vdc (Rx, Tx/Rx) |
50 mA, 60 mA |
|
Consumption in Alarm @ 12 Vdc (Rx, Tx/Rx) |
40 mA, 50 mA |
|
Consumption in Fault @ 24 Vdc (Rx, Tx/Rx) |
35 mA, 45 mA |
|
Consumption in Fault @ 12 Vdc (Rx, Tx/Rx) |
30 mA, 40 mA |
|
Pre-Alarm Obscuration Thresholds |
20%, 25%, 30%, 35% |
|
Alarm Obscuration Threshold |
35% |
|
Minimum Operating Distance |
5 m |
|
Maximum Operating Distance |
150 m (separate Tx and Rx) / 100 m (Tx/Rx and passive reflector) |
|
Wavelenght of the Transmitter Beam |
890 nm |
|
Tolerance to the Beam Misalignment (separate Tx and Rx) |
± 1° |
|
Tolerance to the Beam Misalignment (TxRx unit and passive reflector) |
± 0.5° ; ± 5° |
|
Pre-Alarm Relay |
1A. 30Vdc resistive load – NO/NC contact. Selectable via jumper |
|
Alarm Relay |
1A. 30Vdc resistive load – NO/NC contact. Selectable via jumper |
|
Fault Relay |
1A. 30Vdc resistive load – NO/NC contact. Selectable via jumper |
|
Conventional Detection Circuit – Input Voltage Range |
10 – 20 Vdc |
|
Conventional Detection Circuit – Consumption in Pre-Alarm Condition |
20 mA @ 20 Vdc |
|
Conventional Detection Circuit – Consumption in Alarm Condition |
40 mA @ 20 Vdc |
|
Conventional Detection Circuit – Reset Pulse Duration |
200 ms |
|
Operating Temperature |
From -10°C - 55°C |
|
Relative Humidity |
95% |
|
Protection Grade |
IP55 |
|
Passive Reflector Dimensions |
10 x 10 cm / 20 x 20 cm / 30 x 20 cm |
|
Dimensions |
248 x 122 x 120 mm |
|
Weight |
900 g |