Rated voltage 51.2V Nominal capacity 280Ah Energy capacity 14.34 kWh (14336 Wh) Lifespan of the cycle 6000 cycles (0.2 C, 25°C 80% DOD) Efficiency >98% Self-loading (month) <3% Max. number in parallel circuit 16 pcs. Max. number in serial circuit Not allowed
Recommended charging voltage 56.0V Maximum charging voltage 58.4V Rated working current (order/discharge.) 95A Rated utility power 4.86 kW Maximum available continuous current 200A Maximum available power 10.24 kW
Protection during charging (single cell) 3.7V Overvoltage protection (full battery) 58.4V Protection against low discharge voltage (cell) 2.7V Low discharge voltage protection (battery) 43.2V Short circuit protection YES
First charging current protection 205A (Delay time: 2s) Second charging current protection 210A (Delay time: 1s) First discharge current protection 205A (Delay time: 1s) Second discharge current protection 250A (Delay time: 100ms) Protection against excessive charging voltage 58.4V (Delay time: 1–2 s) Protection against excessive discharge voltage 43.2V (Delay time: 1–2 s) Temperature protection PCB temperature < 95°C, return to normal operation < 85°C Main port of communication CAN, RS485 optional
Charging temperature (0 to 55)°C Discharge temperature (-20 to 60)°C Storage Temperature (-5 to 30)°C
Dimensions (L x W x H) 826 x 415 x 238 mm Net weight 110 kg (+/- 3%) Type of clamps The M8 Terminal Torque of the terminals 8.5 Nm Housing material SPCC Dimensions of unit packaging 988 x 503 x 424 mm Unit Packing Weight 131.5 kg