• Pure sine wave output • Output power factor 0.8 • DSP digital control • Boost and buck AVR for voltage stabilization • Auto sensing frequency • Adjustable charging current and battery shutdown point Settable • ECO mode and no-load shutdown • Humanized alarm system • Power-on self test Cold start • Auto restart when mains power is restored • Intelligent battery management • Short circuit and overload protection • Automatic charging in OFF mode • USB & RJ45, AS400 / SNMP (optional) communication port

CAPACITY

Reactive Power (VA)

3000

Active Power (W)

2400

DC INPUT

Rated voltage

48V

DC input range (default)

40 ~ 60 V

AC INPUT

AC input range (bypass mode)

0 ~ 121 V / 132 V / 138 V / 144 Vac for 100 V / 110 V / 115 V / 120 Vac

± 10 Vac

0 ~ 242 V / 264 V / 276 V / 288 Vac for 200 V / 220 V / 230 V / 240 Vac

± 10 Vac

AC input range (mains mode)

100 V: 70 ~ 130 Vac  /  110 V: 80 ~ 140 Vac  / 115 V: 85 ~ 145 Vac 

120 V: 90 ~ 150 Vac / 200 V: 145 ~ 260 Vac   /  220 V: 165 ~ 280 Vac

230 V: 175 ~ 290 Vac  / 240 V: 185 ~ 300 Vac

Frequency range

50 Hz / 60 Hz (auto-sense)

50 Hz / 60 Hz ± 5% ~ 15%

Generator connection

Available (generator input power is settable)

OUTPUT

inverter output range

100 V / 110 V / 115 V / 120 V / 200 V / 220 V / 230 V / 240 Vac

± 5% (settable)

AC output range (bypass mode)

0 ~ 121 V / 132 V / 138 V / 144 Vac for 100 V / 110 V / 115 V / 120 Vac

± 10 Vac

0 ~ 242 V / 264 V / 276 V / 288 Vac for 200 V / 220 V / 230 V / 240 Vac

± 10 Vac

AC output range (mains mode)

100 V: 90 ~ 110 Vac / 110 V: 99 ~ 115 Vac  / 115 V: 103 ~ 126 Vac

120 V: 108 ~ 132 Vac / 200 V: 166 ~ 226 Vac   /  220 V: 188 ~ 245 Vac

230 V: 199 ~ 254 Vac  / 240 V: 210 ~ 264 Vac

Output frequency

50 / 60 Hz ± 0.3 Hz (settable)

Waveform

Pure sine wave

Inverter efficiency

Max. 85%

Energy saving mode

Settable (< 3% load) , enter in 80 s

No-load shutdown

Settable (< 3% load) , enter in 80 s

Transfer time

≤ 10 ms

THDV (resistive load)

≤ 5%

Protections

Overload, short circuit (inverter), battery low voltage, battery overcharge, overtemperature

Overload (mains mode)

110% for 120 s, 125% for 60 s, 150% for 10 s

(transfer to bypass mode)

Overload (inverter mode)

110% for 60 s, 125% for 10 s, 150% for 5 s

(shut down directly)

Mute

Automatic mute in 60 s or by manual

BATTERIES

Battery capacity (H: external expansion)

12 V / 9 Ah x 4

Charging current

Standard model (S): 1 A (default)

Long time model (H): 10 A (default); <10 A, set step 1 A; ≥ 10 A, set step 5 A

Equalizing charge voltage

Single battery 14.1 Vdc (default), 13.6 ~ 15 Vdc adjustable

Floating charge voltage

Single battery 13.5 Vdc(default)

13.2 ~ 14.6 Vdc adjustable

Low voltage alarm point

Single battery 10.8 Vdc (default)

9.6 ~ 13 Vdc adjustable

Low voltage shutdown point

Single battery 10.2 Vdc (default)

9.6 ~ 11.5 Vdc adjustable

DIMENSIONS TOWER or CABINET

Net / Gross weight (kg)

28.1 / 30.2 (S)

28.0 / 30.0 (H)

Dimensions (W × D × H) (mm)

190 x 467 x 335.5 (S / H)

Packaged dimensions (W × D × H) (mm)

320 x 592 x 462 (S / H)

DIMENSIONS RACK-MOUNT

Net / Gross weight (kg)

26.7  / 30.5 (S)

Dimensions (W × D × H) (mm)

10.24 (Ieskaitot nodokli)
2.34 (Ieskaitot nodokli)
11.25 (Ieskaitot nodokli)
12.96 (Ieskaitot nodokli)
3.17 (Ieskaitot nodokli)
5.47 (Ieskaitot nodokli)
6.30 (Ieskaitot nodokli)
4.73 (Ieskaitot nodokli)
5.55 (Ieskaitot nodokli)
5.55 (Ieskaitot nodokli)
15.60 (Ieskaitot nodokli)

За ту же цену!

BATTERY 25.6V/50AH/LIFEPO4-EP EUROPOWER
25.6V/50AH/LIFEPO4-EP
377.42 (Ieskaitot nodokli)
377.58 (Ieskaitot nodokli)
379.49 (Ieskaitot nodokli)